When an electric current flows through the cable, some energy is lost. She is lost in heating the conductors due to their resistance, with a reduction which increases the magnitude of the transmitted power and the allowable current for copper wires. The most appropriate conductor in practice is copper that has small electric resistance, satisfied consumers of the cost and is available in a wide range.
The Following metal with good conductivity is aluminum. It is cheaper than copper, but more brittle and deformed in the joints. First in-house domestic network was laid aluminum wires. They were hidden under plaster and long forgotten about the wiring. Electricity was mainly spent on lighting, and wires easily withstand the load.
With the development of technology there are many appliances that have become indispensable in the home demanded a larger amount of electricity. The power consumption is increased and the transaction has ceased to cope with it. Now the unthinkable has become doing the electricity of the apartment or home without calculating the wiring capacity. Wires and cables are selected to avoid unnecessary costs, and they are fully handled all of the loads in the house.
Passing the electric current causes heating of the conductor. At high temperatures, the metal oxidizes rapidly, and the insulation begins to melt at a temperature of 65 0C. the more it is heated, the faster it goes down. For this reason, the wire choose the allowable current, which is overheating.
Recommended
The most effective methods of seed germination
Despite the fact that the method of seedling in vegetable production is a very time consuming process, it is used by most gardeners. Planting seeds in open ground is an easy and convenient method, but it is effective only in certain climatic zones. I...
Retro-reflective paint. The scope of
When the vehicle began to fill the road, their popularity began to gain reflective paint. Thanks to this paint, as drivers and pedestrians becomes much easier to avoid accidents in the dark. Purpose paint Reflective paint – paint material, whic...
How to make icon with your own hands - options izgotovleniya (simple and complex)
In Soviet times, many collecting badges, emblems, pennants. To get them was not easy. And today, thanks to technology, you can make them yourself. Knowing how to make icon with your own hands, and you can make original gifts to your friends, and make...
The shape of the wire runs in the form of a circle, square, rectangle, or triangle. From residential wiring-section preferably circular. Copper bus bar is usually in the electrical Cabinet and is rectangular or square.
Square transverse cross-section are determined by the basic dimensions measured by the caliper.
In calculations the following notation:
The Power that is released in the veins of the cable during its operation, determined by the formula: P = IN2Rn
Where IN - load current, a; R - resistance, Ω; n is the number of conductors.
The Formula is suitable for the calculation of one load. If the cable is connected several, a quantity of heat is calculated separately for each consumer of energy, and then the results are summed up.
Allowable current for copper stranded conductors is also calculated through the cross section. It is necessary to fluff up the end, measure the diameter of one of the wires to calculate the area and multiply by their number in the wire.
Wire size is conveniently measured in square millimeters. If roughly estimate the allowable current, mm2 copper wire 10 passes through itself And, while not overheating.
In neighbouring cable wires keep each other warm, so it is necessary to choose the thickness of the cores from tables or amendment. In addition, we take the dimensions with a small margin in the direction of increasing, and then choose from the standard series.
The Transaction can be overt and covert. In the first embodiment, it is laid outside on surfaces, in pipes or in cable ducts. Is hidden under plaster, in ducts or pipes inside structures. Here, working conditions are more stringent as in confined spaces without access of air, the cable heats up stronger.
For different operating conditions are entered coefficients of amendments that need to multiply the estimated long-term permissible current depending on the following factors:
Example
At a load of 5 kW and a voltage of 220V the current through the copper wire will be 5 x 1000 / 220 = 22,7 section A. It will amount to 22.7 / 10 = 2,27 mm2. This size will provide the allowable current for copper wires by heating. So here should take a small margin of 15 %. As a result, the cross-section will be S = 2,27 + 2,27 x 15 / 100 = 2,61 mm2. Now to that size you should pick up a standard wire size, which is 3 mm.
The Conductor can not heat up from passing current indefinitely. At the same time it gives off heat to the environment, the amount of which depends on the temperature difference between them. At some point there comes the equilibrium state and the temperature of the conductor is set constant.
Important! In properly selected transaction the losses for heating are reduced. It should be remembered that wasteful consumption of electric power (when the wires overheat) also have to pay. On the one hand feecharged for excess consumption over the counter, and with another - the replacement of the cable.
For model apartments electricians especially do not think about which cable cross sections to choose from. In most cases, use these:
This system copes with loads, if not powerful appliances, which are sometimes necessary to conduct a separate power supply.
Great in order to find the allowable current copper wire table from the directory. It also lists the calculated data with the use of aluminum.
The Basis for selection of the transaction is the power of consumers. If the total power in the lines from the main input P = 7.4 kW at U = 220 V, allowable current for copper wire will be on the table 34 A, and the cross-section 6 mm2 (closed strip).
The Maximum permissible short-time current for copper wires at operating modes with cycle times up to 10 minutes and work periods of between not more than 4 min is a long operation, if the cross-section not exceeding 6 mm2. In the above cross section 6 mm2: IDOP = IN∙0,875/√TP. V.
Where TP is the ratio of the duration of the working period for the duration of the cycle.
Power-Off at overloads and short circuits is determined by the characteristics of used protective machines. Below is a diagram of a small control room of the apartment. Food from the counter is fed into the opening machine DP MCB with a capacity of 63 A, which protects the wiring to the machines separate lines with a capacity of 10 A, 16 A and 20 A.
Important! The thresholds of the machines must be less than the maximum allowable current of the wiring and above the load current. In this case, each line will be protected.
The Value of the nominal current on the cable input into the apartment depends on how many connected consumers. The table shows the necessary appliances and their power.
Appliance | Nominal power kW |
TV | 0,18 |
Boiler | 2-6 |
Refrigerator | 0,2-0,3 |
Oven | 2-5 |
Cleaner | 0,65-1 |
Electric | 1,2-2 |
Iron | 1,7-2,3 |
Microwave | 0,8-2 |
Computer | 0,3-1 |
Washing machine | 2,5-3,5 |
Lighting System | 0,5 |
Total | A 12.03-23,78 |
The Strength of the current by the known power can be found from the expression:
I = P∙KAnd/(U∙cos φ), where KAnd = 0,75 - coefficient of simultaneity.
For most electrical devices in the active load, the power factor cos φ = 1. Fluorescent lamps, motors, vacuum cleaner, washing machine etc. it is less than 1 and must be taken into account.
Long-term allowable current for the devices shown in the table, will be I = 41 - 81 A. the Value obtained is quite impressive. You should always think twice when buying a new appliance, pull it to its network of apartment. On the table for open wiring-section input wire will be 4-10 mm2. Here still it is necessary to consider how the housing burden will affect obschedomovoe. It is possible that the housing office will not allow you to connect as many appliances to the standpipe entrance, where through the cabinets under each phase and the neutral is the busbar (copper or aluminum). They simply will not pull the meter which is normally installed in the panel on the landing. In addition, the fee for excess of norms of electric power will grow to impressive sizes due to the multiplying coefficients.
If the wiring to do for a private home, there is need to take into account the power outlet wires from the main network. Commonly used aluminum wires of SIP-4 section 12 mm2 may not be enough for a large load.
After the selected cable to connect to the network and it is selected to protect against overloads and short circuits automatic input, you need to select wire for each group of consumers.
Load is divided into light and power. The most powerful consumer in the house is the kitchen, which sets the cooker, washing machine and dishwasher, fridge, microwave and other appliances.
For each outlet selected wire 2.5 mm2. The table for hidden wires, he will miss 21 A. Scheme supply usually radial from the fuse box. Therefore, the box must be suitable leads 4 mm2. If the socket is connected by train, note that the cross section of 2.5 mm2 corresponds to a capacity of 4.6 kW. Therefore, the total load on them must not exceed. There is one drawback: in case of failure of one outlet, the rest can also not be functional.
Boiler, electric stove, air conditioning and other powerful load, it is advisable to connect a separate wire with a gun. The bathroom is a separate input with a gun andOuzo.
The lighting wire is 1.5 mm2. Now many use the basic and additional lighting where you may need a bigger section.
The calculation of the permitted cable cross-section is affected by the network type. If power consumption is the same, the allowable Ampacity of the conductor cable for three-phase mains will be smaller than for single-phase.
To power the three wire cable at U = 380 V formula is applied:
I = P/(√3∙U∙cos φ).
Power Factor can be found in the characteristics of electrical appliances or it is equal to 1, if the load is active. Maximum allowable current for copper wire and aluminum with three-phase voltage is indicated in the tables.
To prevent overheating of the conductors under continuous load properly calculate transverse cross-section, which depends on the allowable current for copper wires. If the capacity of the conductor is insufficient, the cable will fail prematurely.
Article in other languages:
DE: https://tostpost.com/de/gem-tlichkeit/8865-der-maximal-zul-ssige-strom-f-r-kupferdr-hte.html
KK: https://tostpost.com/kk/domashniy-uyut/8868-barynsha-r-sat-et-let-n-tok-sh-n-mys-sym.html
PT: https://tostpost.com/pt/o-aconchego-do-lar/8863-m-xima-admiss-vel-para-fios-de-cobre.html
TR: https://tostpost.com/tr/domashniy-uyut/8872-zin-verilen-en-fazla-ak-m-bak-r-tel.html
Alin Trodden - author of the article, editor
"Hi, I'm Alin Trodden. I write texts, read books, and look for impressions. And I'm not bad at telling you about it. I am always happy to participate in interesting projects."
Related News
How to make a 3D self-leveling floor with their hands?
Sooner or later in everyone's life there is a terrible word – “repair”. Very often, even small changes spread over weeks and months, and the estimate is growing steadily. But if to approach to business responsibl...
Accuracy classes of measuring instruments. Instrumentation. 5 accuracy class
high-Precision devices are used in various fields of life and production of modern society. Without special equipment there would be space travel, development of military and civilian equipment, and more. Repair of such equipment ...
What sand is needed for the Foundation: river or pit? The choice of sand for construction
Before starting construction work, a pre-calculate the necessary amount of material. This is the correct approach to such a serious case. But at this stage raises a lot of questions. One of them is: what kind of sand is needed for...
How to visually increase the height of the ceiling: designer tips
Repair – a complex, time-consuming and costly. Getting to him, everyone is hoping for a good result, which will be the reward for hard work and effort. Therefore, it is important to consider all the details.Thinking about ho...
Bonsai: how to grow from seed. Growing bonsai from pine, oak, maple
Bonsai – is a small tree with a trunk and crown fanciful. Its history stretches back to ancient times in China, but in Japan, bonsai has evolved from simply unusual plants in the present art. Today, and the trees themselves,...
Masonry barbecue-brick stoves - the description of technology, design, and recommendations
If you have a house with a spacious plot, then you should think about the layout, where will be located the furnace. This design can fulfill the function of barbecue and make it yourself. In the end, manage to get a device that wi...
Comments (0)
This article has no comment, be the first!